欢迎光临~科士达UPS_科士达UPS官网_电源精密空调官网 4007655808
语言选择: 中文版 ∷  英文版

公司新闻

在使用科士达UPS电源前要做那些检查

为了确保数据中心科士达UPS电源系统的性能符合正常运行的要求,在科士达UPS电源投入数据中心带载运行前,必须对科士达UPS电源及其相关的系统进行系统化测试,包括:电气性能,物理连接,工作环境等检查。检查系统采集和存储运行参数功能:主输入电压、旁路输入电压、输出电压、输出电流、输出频率、蓄电池电压,充/放电电流,蓄电池温度等。

一、科士达UPS电源系统静态检查

科士达UPS电源输入、输出参数检查:输入输出电压、电流、频率、功率、功率因数、电压谐波失真度。

科士达UPS电源输入过、欠电压保护检查:

1.模拟输入电压超出允许变化范围状态,检测科士达UPS电源系统是否可以自动转为电池供电;

2.模拟输入电压恢复正常范围状态,检测科士达UPS电源系统是否可自动从电池逆变转为正常工作方式。

输出过、欠电压保护检查:检测系统逆变输出电压超过设定过、欠电压值时,系统是否告警,并装完旁路供电状态。

系统断路器保护检测:检测系统的交流主输入、旁路输入和交流输出断路器保护装置是否合格正常。

科士达UPS电源监控性能检测:检查UPS系统RS232或RS485/422、IP/USB等标准通讯接口工作情况;系统正常工作/电池逆变/旁路供电、过载、蓄电池放电电压低、市电故障、功率模块状态。

In order to ensure that the performance of the UPS power system in the data center meets the requirements of normal operation, it is necessary to systematically test the UPS power supply and its related systems before the UPS power is put into the data center for on-load operation, including electrical performance, physical connection, working environment and so on. The functions of collecting and storing operation parameters are checked: main input voltage, bypass input voltage, output voltage, output current, output frequency, battery voltage, charging/discharging current, battery temperature, etc.
I. Static Inspection of UPS Power Supply System in Costa
Inspection of input and output parameters of Kosta UPS power supply: input and output voltage, current, frequency, power, power factor, voltage harmonic distortion.
Over-input and under-voltage protection check of Kosta UPS power supply:
1. Analog input voltage beyond the allowable range of change state, testing whether the Corstal UPS power supply system can be automatically converted to battery power supply;
2. Analog the input voltage to return to the normal range, check whether the Corstal UPS power supply system can automatically change from battery inversion to normal operation mode.
Output and undervoltage protection check: detect whether the system alarms when the output voltage of the inverters exceeds the set overvoltage and undervoltage value, and install the bypass power supply state.
System Circuit Breaker Protection Testing: Testing whether the AC main input, bypass input and AC output circuit breaker protection devices of the system are qualified and normal.
Testing the performance of UPS power supply monitoring: check the working status of UPS system RS232 or RS485/422, IP/USB and other standard communication interfaces; normal operation of the system / battery inversion / bypass power supply, overload, low battery discharge voltage, power failure, power module status.

二、科士达UPS电源环境及外观检查

设备的备用电源系统空间的清洁状况

机房内部的温湿度

机房内部灰尘及洁净度

机房内部地板和屋顶防水情况

机房楼板承重情况

三、科士达UPS电源外部链接检查

科士达UPS电源输入输出连接线是否牢固可靠

配电系统输出输入开关柜内部和外部接线是否牢固

开关柜安装是否稳固,相关操作机构动作是否灵活

配电柜中断路器整定值设置是否准确无误

配电柜内设备及电气器件是否连接紧固

科士达UPS电源系统调试工程师主要准备测量仪表包括:接地电阻测试仪,红外测温仪,电能质量分析仪,万用表,许电池内阻测量仪等。

电能质量分析仪主要用于测量UPS的所以电气参数,红外测量仪主要用于测量电路连接点,电池外接点,开关柜中断,以及各连接器件的工作温度。蓄电池内阻测量仪,测量UPS所配置的蓄电池的内阻,并由此判断蓄电池的好坏。

II. Environmental and Appearance Inspection of UPS Power Supply in Costa
Cleaning status of spare power system space of equipment
Temperature and Humidity in Computer Room
Dust and cleanliness in engine room
Waterproofing of the floor and roof inside the machine room
Load-bearing condition of floor in computer room
III. External Link Check of UPS Power Supply in Costa
Is the Input and Output Connecting Wire of Corstal UPS Power Source Firm and Reliable
Is the internal and external wiring of the output and input switchgear of the distribution system firm?
Is the installation of switchgear stable and the operation mechanism flexible?
Whether the setting value of circuit breaker in distribution cabinet is correct or not
Are the equipments and electrical devices in the distribution cabinet tightly connected?
The Commissioning Engineer of Kosta UPS power supply system mainly prepares measuring instruments including grounding resistance tester, infrared thermometer, power quality analyzer, multimeter, allowable battery internal resistance tester, etc.
Power quality analyzer is mainly used to measure the electrical parameters of UPS. Infrared measurement instrument is mainly used to measure circuit connection points, battery external contacts, switch cabinet interruption, and the working temperature of various connectors. Battery internal resistance measuring instrument measures the internal resistance of UPS battery and judges the quality of battery.

四、科士达UPS电源系统动态检查

科士达UPS电源带满载测试检查:确定UPS设备运行正常,负载连接线安装是否正确,测试设备和检测仪表是否连接正确;

科士达UPS电源负载过载测试检查:负载超过额定负载时设备是否告警,负载超过逆变带载能力时,系统是否切旁路;

科士达UPS电源负载切换测试检查:根据负载切换测试要求调整UPS带载量的大小,一般测试负载量为:0%-30%-80%-100%;

负载切换过程中测量UPS输出电压值,电流值,相位值等技术参数;

科士达UPS电源并联运行测试检查:并联系统带载量及负载均分情况,并机系统切换旁路测试,系统技术参数、警报功能、电池放电等测试.

五、蓄电池系统检查

电池外观检查:电池及电池柜外观完好,线缆连接牢固,接线端子紧固牢固,电池及电池柜内部无漏液痕迹;

电池系统开关和配线检查:电池组开关选择正确,整定值设置合理;

电池内阻测试检查:对每只电池进行内阻测试,记录电池内阻阻值,通过分析比较确定内阻无异常电池;

检测电池组充放电特性:进行电池组浮充测试、匀充测试、自动温度补偿测试、电池组放电及记录;

电池压低保护测试:模拟UPS系统在电池逆变工作方式时,电池电压降至保护点,检测系统放出声光警告,电池停止供电.

六、科士达UPS电源使用

使用科士达UPS电源可以解决两个方面的问题,就是意外断电和市电品质差时,UPS电源可以提供及时的供电,保证正常的工作运行和正常的工作效率。

科士达UPS电源的两大主要功能:

1、应急使用:防止意外断电而影响正常工作。

2、日常使用:消除市电上的电涌,瞬间高电压,瞬间低电压,电线噪声和频率偏移等电源污染,改善电源质量,提供高质量的电源。

对于这些两大功能,就是一些关于科士达UPS电源的使用经验大家可以借鉴:

1、带载过轻有可能造成电池的深度放电,分降低电池的使用寿命。

2、适当的放电有助于电池的激活.如长期不停市电,每3月也应人为断掉市电用UPS带负载放电一次,可以延长电池使用寿命。

3、多数小型UPS,上班再开启,且开机时避免带载启动,下班应关闭UPS;对于网络机房的UPS,则可全天候运行。

4、勿带感性负载,如点钞机,日光灯,空调等,以免造成损害.输出负载控制在60%左右为佳,可靠性较高。

IV. Dynamic Inspection of UPS Power Supply System in Costa
Corstal UPS power supply with full load test check: to determine whether UPS equipment is running normally, whether the load connection line is installed correctly, whether the test equipment and test instrument are connected correctly;
Corstal UPS power load overload test check: Whether the equipment alarms when the load exceeds the rated load, and whether the system cuts the bypass when the load exceeds the load carrying capacity of the inverters;
Load switching test and inspection of Kosta UPS power supply: adjust the load of UPS according to the load switching test requirements, the general test load is: 0% - 30% - 80% - 100%;
In the process of load switching, UPS output voltage value, current value, phase value and other technical parameters are measured.
Testing and checking of parallel operation of Kosta UPS power supply: parallel system with load and load sharing, parallel system switching bypass test, system technical parameters, alarm function, battery discharge test, etc.
V. Inspection of Battery System
Battery Appearance Inspection: Battery and battery cabinet appearance is intact, cable connection is firm, wiring terminal is firm, no leakage marks inside the battery and battery cabinet;
Battery system switch and wiring check: Battery switch selection is correct, setting value is reasonable;
Battery internal resistance test and inspection: each battery is tested for internal resistance, and the value of internal resistance is recorded. Through analysis and comparison, the battery with no abnormal internal resistance is determined.
Charging and discharging characteristics of battery packs were tested: floating charge test, uniform charge test, automatic temperature compensation test, battery discharging and recording.
Battery Voltage Lowering Protection Test: Simulate UPS system when the battery inverted mode of operation, the battery voltage drops to the protection point, the detection system emits sound and light warnings, and the battery stops power supply.
VI. USE OF UPS POWER SUPPLY IN COSTA
The use of Corstal UPS power supply can solve two problems, that is, when unexpected power outages and poor quality of electricity, UPS power supply can provide timely power supply to ensure normal operation and normal working efficiency.
Two main functions of Kosta UPS power supply:
1. Emergency use: prevent accidental power failure and affect normal work.
2. Daily use: eliminating power pollution, such as surge, instantaneous high voltage, instantaneous low voltage, wire noise and frequency offset, to improve the quality of power supply and provide high-quality power supply.
For these two functions, we can draw lessons from the experience of using Corstal UPS power supply.
1. Light overload may cause deep discharge of batteries and reduce the service life of batteries.
2. Appropriate discharge is helpful to the activation of batteries. If power is not on the market for a long time, UPS with load should be discharged artificially every 3 months, which can prolong the service life of batteries.
3. Most small UPS should be turned on again at work, and avoid start-up with load, and should be shut down after work. For UPS in network computer room, it can run all-weather.
4. Don't bring inductive load, such as money counter, fluorescent lamp, air conditioner, etc., to avoid damage. Output load control is better at about 60%, which has high reliability.

从主电路结构和不间断供电的运行机制来看,目前技术成熟并已经形成产品的各种科士达UPS电源主要有四大类:后备式UPS,在线互动式UPS,双变换在现实UPS以及双向变换串并联补偿在线式UPS。

科士达UPS电源通常由输入整流滤波电路、功率因数校正电路、蓄电池组、充电电路、逆变电路、静态开关电路、控制检测见识及保护电路共7个部分组成。

科士达UPS电源输入整流滤波电路

科士达UPS电源中,常用的整流电路有单相不可控和可控整流电路、三相不可控和可控整流电路。滤波器可分为电容输入或电感输入两种。电容输入滤波器的输出电压较高,但要求变压器输出的缝制电流较大,且负载调整交。电感输入滤波器的输出特定较好,但需要较大的扼流圈且成本较高。目前UPS中通常采用电容和电感组成的LC滤波器。

科士达UPS电源功率因数校正电路

科士达UPS电源中,交流市电经整流后都采用大容量电容器进行滤波,而且整流电路输出端还并联有蓄电池。在电容器或蓄电池充电期间将形成脉冲电流。该电流峰值很高,会产生高次谐波电流并导致功率因数下降,功率因数校正电路可使电网输入电流变为与输入电压同相位的正弦波。

科士达UPS电源蓄电池组

蓄电池组是UPS的心脏。市电正常时,蓄电池充电,将电能转化为化学能,并储藏起来,市电中断时,UPS蓄电池中电量维持逆变器工作。目前,中小型UPS中广泛使用阀控铅酸蓄电池。在长延时(4h或8h)的UPS中,蓄电池的成本甚至超过主机的成本。正确使用蓄电池组,对延长蓄电池的使用寿命只管重要。使用正确,阀控铅酸电池的寿命可达10年以上。

科士达UPS电源充电电路

科士达UPS电源中,一般充电电路都是独立工作的,也就是说,即使不使用逆变器,只要将交流电源接通,充电电路就开始工作,在充电过程中,首先采用恒流充电,当蓄电池的电压达到浮充电压后,再转为恒压充电,直到电池被充足。因此,充电电路一般有两个反馈回路,一个做电流反馈,一个做电压反馈。主电路一般采用开关型整流电路。为了缩短充电时间,各种快速充电电路在UPS中也得到应用。

Corstal UPS Power Factor Correction Circuit
In Kosta UPS power supply, AC power is filtered by large capacity capacitors after rectification, and the output terminal of rectifier circuit is also connected with batteries in parallel. Pulse current will be formed during the charging of capacitors or batteries. The peak value of the current is very high, which will produce high harmonic current and lead to the decrease of power factor. The power factor correction circuit can make the input electrorheology of the power grid into sinusoidal wave in phase with the input voltage.
Corstal UPS Power Battery Set
Battery packs are the heart of UPS. When the city electricity is normal, the battery is charged, the electric energy is converted into chemical energy, and stored. When the city electricity is interrupted, the power in UPS battery maintains the inverters working. At present, VRLA batteries are widely used in small and medium-sized UPS. In UPS with long delay (4h or 8h), the cost of batteries is even higher than that of mainframe. Correct use of batteries is very important for prolonging the service life of batteries. The service life of VRLA batteries can reach more than 10 years if they are used correctly.
Corstal UPS Power Charging Circuit
In Kosta UPS power supply, the charging circuit generally works independently. That is to say, even if no inverter is used, as long as AC power is connected, the charging circuit will start to work. In the charging process, constant current charging is used first, and when the battery voltage reaches the floating charging voltage, it will be changed to constant voltage charging until the battery is sufficient. Therefore, charging circuits generally have two feedback loops, one for current feedback and the other for voltage feedback. Switching rectifier circuit is generally used in the main circuit. In order to shorten the charging time, various fast charging circuits are also used in UPS.

科士达UPS电源逆变电路

逆变器的作用是将市电整流后的直流电压或蓄电池电压变换成交流电压。在后备式UPS中,逆变器输出电压波形一般为准方波;在在线式UPS,中,逆变器输出电压多为正弦波脉宽调制(SPWM)波形,该波形经LC滤波器滤波后,可得到标准正弦波。

科士达UPS电源静态开关电路

静态开关的作用是保护UPS和负载,并实现市电旁路供电和逆变器供电的转换。UPS过载是,为了保护逆变器,当市电正常时,UPS通过静态开关将输出有逆变器转换到市电;当逆变器出现故障时,为了保证负载不断电,UPS的输出也通过静态开关输出切换到市电。由于UPS内部一般都有同步锁相电路,同时静态开关转换时间段,因此在转换过程中不会出现供电间断。小型UPS一般采用快速继电器作为静态开关,大、中型UPS则采用反响并联的快速晶闸管作为静态开关。

科士达UPS电源监控、检测、显示保护电路

科士达UPS电源输出电压的精度、波形失真度以及工作可靠性均与控制电路密切相关。控制电路主要有SPWM产生电路,闭环调压电路、同步锁相电路等。为了UPS可靠工作,还应具有较完善的保护电路。一般的UPS中都有电池电压过低自动保护电路、市电电压过高自动和UPS延迟启动自动保护电路等。为了随时掌握和了解工作状态及其运行情况,UPS中还设有监测电路、显示电路及报警电路。

科士达UPS电源的分类:

1.按照功率分类:<5KVA,5-20KVA,>20KVA

2.按照输入输出电压分类:单相UPS,三相UPS

3.按照安装方式分类:塔式,机架式。

4.按照技术分类:后备,在线互动式,双变换在线式,Delta变换式。

5.按照结构分:模块化UPS,固定功率UPS,类模块化UPS

6.固定功率在线式分类:工频机,IGBT整流器+传统逆变器(过渡技术),高频机

1.2.1按电路主结构分类

(1)后备式UPS

(2)在线式UPS

(3)串并联调整式UPS

(4)在线互动式UPS

1.2.2按后备时间分类

(1)标准机

(2)长效机

1.2.3按输入/输出方式分类

(1)单相输入/单相输出UPS(小功率UPS)

(2)三相输入/单相输出UPS(中、大功率UPS)

(3)三相输入/三相输出UPS(中、大功率UPS)

对于用户来说,采用三相供电时市电配电和负载配电比较容易,每一相都承载一部分负载电流。

1.2.4

按输出波形分类

(1)正弦波UPS

(2)方波UPS

不适合带感性负载,会使方波产生瞬态尖波,从而给UPS和负载设备造成破坏,大多数后备式UPS的输出波形为方波。

1.2.5按输出容量分类

(1)微型UPS(输出功率小于或等于1kVA)

(2)小型UPS(输出功率大于1kVA而小于5kVA)

(3)中型UPS(输出功率大于5kVA而小于或等于30kVA)

(4)大型UPS(输出功率大于30kVA而小于或等于100kVA)。

1.3技术成熟并已形成产品的UPS,按技术性能的优劣来排序

(1)双变换在线式UPS

(2)串并联调整式UPS(Delta变换器)

(3)在线互动式UPS

(4)后备式正弦波UPS

(5)后备式方波UPS

在使用科士达UPS电源系统的过程中,人们往往片面地认为蓄电池是免维护的而不加重视。然而有资料显示,因蓄电池故障而引起UPS主机故障或工作不正常的比例大约为1/3。由此可见,加强对UPS电池的正确使用与维护,对延长蓄电池的使用寿命,降低UPS系统故障率,有着越来越重要的意义。除了选配正规品牌蓄电池以外,应从以下几个方面入手正确地使用与维护蓄电池:


一、保持适宜的环境温度。影响蓄电池寿命的重要因素是环境温度,一般电池生产厂家要求的最佳环境温度是在20-25℃之间。虽然温度的升高对电池放电能力有所提高,但付出的代价却是电池的寿命大大缩短。据试验测定,环境温度一旦超过25℃,每升高10℃,电池的寿命就要缩短一半。目前UPS所用的蓄电池一般都是免维护的密封铅酸蓄电池,设计寿命普遍是5年,这在电池生产厂家要求的环境下才能达到。达不到规定的环境要求,其寿命的长短就有很大的差异。另外,环境温度的提高,会导致电池内部化学活性增强,从而产生大量的热能,又会反过来促使周围环境温度升高,这种恶性循环,会加速缩短电池的寿命。

二、定期充电放电。科士达UPS电源中的浮充电压和放电电压,在出厂时均已调试到额定值,而放电电流的大小是随着负载的增大而增加的,使用中应合理调节负载,比如控制微机等电子设备的使用台数。一般情况下,负载不宜超过UPS额定负载的60%。在这个范围内,电池的放电电流就不会出现过度放电。

科士达UPS电源因长期与市电相连,在供电质量高、很少发生市电停电的使用环境中,蓄电池会长期处于浮充电状态,日久就会导致电池化学能与电能相互转化的活性降低,加速老化而缩短使用寿命。因此,一般每隔2-3个月应完全放电一次,放电时间可根据蓄电池的容量和负载大小确定。一次全负荷放电完毕后,按规定再充电8小时以上。

三、科士达UPS电源利用通讯功能。目前,绝大多数大、中型UPS都具备与微机通讯和程序控制等可操作性能。在微机上安装相应的软件,通过串/并口连接UPS,运行该程序,就可以利用微机与UPS进行通讯。一般具有信息查询、参数设置、定时设定、自动关机和报警等功能。通过信息查询,可以获取市电输入电压、科士达UPS电源输出电压、负载利用率、电池容量利用率、机内温度和市电频率等信息;通过参数设置,可以设定UPS基本特性、电池可维持时间和电池用完告警等。通过这些智能化的操作,大大方便了UPS电源及其蓄电池的使用管理。

四、及时更换废/坏电池。目前大中型UPS电源配备的蓄电池数量,从3只到80只不等,甚至更多。这些单个的电池通过电路连接构成电池组,以满足UPS直流供电的需要。在UPS连续不断的运行使用中,因性能和质量上的差别,个别电池性能下降、储电容量达不到要求而损坏是难免的。当电池组中某个/些电池出现损坏时,维护人员应当对每只电池进行检查测试,排除损坏的电池。更换新的电池时,应该力求购买同厂家同型号的电池,禁止防酸电池和密封电池、不同规格的电池混合使用。

科士达UPS电源日常维护与检修:

科士达UPS电源在正常使用情况下,主机的维护工作很少,主要是防尘和定期除尘。特别是气候干燥的地区,空气中的灰粒较多,机内的风机会将灰尘带入机内沉积、当遇空气潮湿时会引起主机控制紊乱造成主机工作失常,并发生不准确告警,大量灰尘也会造成器件散热不好。一般每季度应彻底清洁一次。其次就是在除尘时,检查各连接件和插接件有无松动和接触不牢的情况。

(2)虽说储能电池组目前都采用了免维护电池,但这只是免除了以往的测比、配比、定时添加蒸馏水的工作。但外因工作状态对电池的影响并没有改变,不正常工作状态对电池造成的影响没有变,这部分的维护检修工作仍是非常重要的,科士达UPS电源系统的大量维修检修工作主要在电池部分。

a.储能电池的工作全部是在浮充状态,在这种情况下至少应每年进行一次放电。放电前应先对电池组进行均衡充电,以达全组电池的均衡。要清楚放电前电池组已存在的落后电池。放电过程中如有一只达到放电终止电压时,应停止放电,继续放电先消除落后电池后再放。

b.核对性放电,不是首先追求放出容量的百分之多少,而是要关注发现和处理落后电池,经对落后电池处理后再作核对性放电实验。这样可防止事故,以免放电中落后电池恶化为反极电池。

c.平时每组电池至少应有8只电池作标示电池,作为了解全电池组工作情况的参考,对标示电池应定期测量并做好记录。

d.日常维护中需经常检查的项目有:清洁并检测电池两端电压、温度;连接处有无松动,腐蚀现象、检测连接条压降;电池外观是否完好,有无壳变形和渗漏;极柱、安全阀周围是否有酸雾逸出;主机设备是否正常。

e.免维护电池要维护,不是什么无稽之谈,应从广义的维护立场出发,做到运行、日常管理的周到、细致和规范性,保证设备(包括主机设备)保持良好的运行状况,从而延长使用年限;保证直流母线经常保持合格的电压和电池的放电容量;保证电池运行和人员的安全可靠。这就是电池维护的目的,也是电池运行规程中包括的内容和进行规则。

(3)当科士达UPS电源系统出现故障时,应先查明原因,分清是负载还是UPS电源系统;是主机还是电池组。虽说UPS主机有故障自检功能,但它对面而不对点,对更换配件很方便,但要维修故障点,仍需做大量的分析、检测工作。另外如自检部分发生故障,显示的故障内容则可能有误。

(4)对主机出现击穿,断保险或烧毁器件的故障,一定要查明原因并排除故障后才能重新启动,否则会接连发生相同的故障。

(5)当电池组中发现电压反极、压降大、压差大和酸雾泄漏现象的电池时,应及时采用相应的方法恢复和修复,对不能恢复和修复的要更换,但不能把不同容量、不同性能、不同厂家的电池联在一起,否则可能会对整组电池带来不利影响。对寿命已过期的电池组要及时更换,以免影响到主机。

科士达YDE2060    UPS电源

科士达YDE1200    UPS电源

科士达YDC9101S  UPS电源

科士达YDC9101H  UPS电源

科士达YDC9102S  UPS电源

科士达YDC9102H  UPS电源

科士达YDC9103S  UPS电源

科士达YDC9103H UPS电源

科士达YDC9106H  UPS电源

科士达YDC9110H  UPS电源

科士达YDC9106S  UPS电源

科士达YDC9110S  UPS电源

科士达YDC9310H  UPS电源

科士达YDC9315H  UPS电源

科士达YDC9320H  UPS电源

科士达YDC3310     UPS电源

科士达YDC3315     UPS电源

科士达YDC3320     UPS电源

科士达YDC3330     UPS电源

联系我们

联系人:王培

手机:15210159464

电话:400-7655-808

邮箱:15210159464@126.com

地址: 北京市大兴区旧桥路25号院3号楼2层205